Cable: SWA Cables
Download as PDF
Table 4E4A – Current Carrying Capacity in Ampere
- Current Rating Chart for Multicore Armoured
- Thermoplastic Insulated Cables with Copper
- Conductors at 90°C Operating Temperature Extract from the IEE Wiring Regulations, 17th Edition
- 30°C Ambient Air Temperature,
- 90°C Conductor Operating Temperature,
- 20°C Ambient Ground Temperature
Conductor cross-sectional area mm² | REFERENCE METHOD C - CLIPPED DIRECT | Method D - Direct or in ducts, in ground, in/around buildings. | Method E - In free air or on a perforated cable tray. | |||
---|---|---|---|---|---|---|
1 two-core* cable, single | 1 three-core* or 1 four-core | 1 two-core* cable, single | 1 three-core* or 1 four-core | 1 two-core* cable, single | 1 three-core* or 1 four-core | |
phase A.C or D.C. | cable, three-phase A.C. | phase A.C or D.C. | cable, three-phase A.C. | phase A.C or D.C. | cable, three-phase A.C. | |
1.5 | 27 | 23 | 25 | 21 | 29 | 25 |
2.5 | 36 | 31 | 33 | 28 | 39 | 33 |
4 | 49 | 42 | 43 | 36 | 52 | 44 |
6 | 62 | 53 | 53 | 44 | 66 | 56 |
10 | 85 | 73 | 71 | 58 | 90 | 78 |
16 | 110 | 94 | 91 | 75 | 115 | 99 |
25 | 146 | 124 | 116 | 96 | 152 | 131 |
35 | 180 | 154 | 139 | 115 | 188 | 162 |
50 | 219 | 187 | 164 | 135 | 228 | 197 |
70 | 279 | 238 | 203 | 167 | 291 | 251 |
95 | 338 | 289 | 239 | 197 | 354 | 304 |
120 | 392 | 335 | 271 | 223 | 410 | 353 |
150 | 451 | 386 | 306 | 251 | 472 | 406 |
185 | 515 | 441 | 343 | 281 | 539 | 463 |
240 | 607 | 520 | 395 | 324 | 636 | 546 |
300 | 698 | 599 | 446 | 365 | 732 | 628 |
400 | 787 | 673 | 847 | 728 |
Table 4E4B – Voltage drop per ampere, per metre 70°C conductor operating temperature
Conductor crosssectional area mm² | Two-core cable, D.C. | Two-core cable, single phase A.C. | Three or four-core cable, three-phase A.C. | ||||
---|---|---|---|---|---|---|---|
mV/A/m | mV/A/m | mV/A/m | |||||
1.5 | 31 | 31 | 27 | ||||
2.5 | 19 | 19 | 16 | ||||
4 | 12 | 12 | 10 | ||||
6 | 7.9 | 7.9 | 6.8 | ||||
10 | 4.7 | 4.7 | 4.0 | ||||
16 | 2.9 | 2.9 | 2.5 | ||||
r | x | z | r | x | z | ||
25 | 1.850 | 1.850 | 0.160 | 1.900 | 1.600 | 0.140 | 1.650 |
35 | 1.350 | 1.365 | 0.155 | 1.365 | 1.150 | 0.135 | 1.150 |
50 | 0.980 | 0.990 | 0.155 | 1.000 | 0.860 | 0.135 | 0.870 |
70 | 0.670 | 0.670 | 0.150 | 0.690 | 0.590 | 0.130 | 0.600 |
95 | 0.490 | 0.500 | 0.150 | 0.520 | 0.473 | 0.130 | 0.450 |
120 | 0.390 | 0.400 | 0.145 | 0.420 | 0.340 | 0.130 | 0.380 |
150 | 0.310 | 0.320 | 0.145 | 0.350 | 0.280 | 0.125 | 0.300 |
185 | 0.250 | 0.260 | 0.145 | 0.290 | 0.220 | 0.125 | 0.260 |
240 | 0.195 | 0.200 | 0.140 | 0.240 | 0.175 | 0.125 | 0.210 |
300 | 0.155 | 0.160 | 0.140 | 0.210 | 0.140 | 0.120 | 0.185 |
400 | 0.120 | 0.130 | 0.140 | 0.190 | 0.115 | 0.120 | 0.165 |
Download as PDF