Technical Resources
We have gathered together a number of technical resources for use as reference on electrical projects.
DISCLAIMER: The information on this page and the PDF is for information only and R&M Electrical Group Ltd can not be held liable for any information therein.
501/453 UNIVERSAL Hazardous Area Cable Gland
Flameproof Exd & Increased Safety Exe & Restricted Breathing ExnR Dual Certified ATEX / IECEx
Download as PDF
Application
- Outdoor or indoor use.
- For use with single wire armour ‘W’, wire braid ‘X’, steel tape armour ‘Z’, elastomer and plastic insulated cables.
- For particular use with Cables that exhibit ‘Cold Flow’ characteristics.
- See technical section for installation rules and regulations.

Cable Gland Selection Table
Size Ref. | Entry Thread Size | Cable Acceptance Details | 'G' | Hexagon Dimensions | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Metric | NPT * Standard or Option | Inner Sheath 'A' | Outer Sheath 'B' | Armour / Braid 'C' | Across Flat | Across Corners |
|||||
Min. | Max. | Min. | Max. | Orientation 1 | Orientation 2 | ||||||
Os | M20² | ½" | 3.5 | 8.1 | 5.5 | 12.0 | 0.8 / 1.25 | 0.0 / 0.8 | 61.6 | 24.0 | 26.5 |
O | M20² | ½" | 6.5 | 11.4 | 9.5 | 16.0 | 0.8 / 1.25 | 0.0 / 0.8 | 61.6 | 24.0 | 26.5 |
A | M20 | ¾" or ½" | 8.4 | 14.3 | 12.5 | 20.5 | 0.8 / 1.25 | 0.0 / 0.8 | 63.0 | 30.0 | 32.5 |
B | M25 | 1" or ¾" | 11.1 | 19.7 | 16.9 | 26.0 | 1.25 / 1.6 | 0.0 / 0.7 | 69.9 | 36.0 | 39.5 |
C | M32 | 1¼" or 1" | 17.6 | 26.5 | 22.0 | 33.0 | 1.6 / 2.0 | 0.0 / 0.7 | 73.2 | 46.0 | 50.5 |
C2 | M40 | 1½" or 1¼" | 23.1 | 32.5 | 28.0 | 41.0 | 1.6 / 2.0 | 0.0 / 0.7 | 77.9 | 55.0 | 60.6 |
D | M50 | 2" or 1½" | 28.9 | 44.4 / 42.3¹ | 36.0 | 52.6 | 1.8 / 2.5 | 0.0 / 1.0 | 93.5 | 65.0 | 70.8 |
E | M63 | 2½" or 2" | 39.9 | 56.3 / 54.3¹ | 46.0 | 65.3 | 1.8 / 2.5 | 0.0 / 1.0 | 94.0 | 80.0 | 88.0 |
F | M75 | 3" or 2½" | 50.5 | 68.2 / 65.3¹ | 57.0 | 78.0 | 1.8 / 2.5 | 0.0 / 1.0 | 103.0 | 95.0 | 104.0 |
G | M80 | 3½" | 67.0 | 73.0 | 75.0 | 89.5 | 2.0 / 3.5 | 0.0 / 1.0 | 90.6 | 106.4 | 115.0 |
H | M90 | 3½" | 67.0 | 77.6 | 75.0 | 89.5 | 2.0 / 3.5 | 0.0 / 1.0 | 90.6 | 115.0 | 130.0 |
J | M100 | 4" | 75.0 | 91.6 | 88.0 | 104.5 | 2.5 / 4.0 | 0.0 / 1.0 | 90.6 | 127.0 | 142.0 |
All dimensions in millimetres (except * where dimensions are in inches). Os – F size metric entry threads are 1.5mm pitch as standard, 15mm length of thread. For G size glands and above, a 2mm pitch is supplied as standard, 20mm length of thread (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering. G size and above are available in the 501/453/RAC design style.
¹ Smaller value is applicable when selecting reduced NPT entry option.
² Sizes Os and O are available with an M16 thread size. For O size with M16 thread, the maximum cable inner sheath diameter is 10.9mm
Technical Data
- Flameproof Exd and Increased Safety Exe II 2 GD ExtD A21 and Restricted Breathing ExnR II 3G.
- Certificate No’s: For sizes Os to F: Baseefa06ATEX0057X and IECEx BAS 06.0014X. For sizes G to J: Baseefa06ATEX0056X and IECEx BAS 06.0013X.
- Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
- Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15, IEC/EN 61241-0 and IEC/EN 61241-1.
- Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
- Deluge Protection to DTS01.
- Operating Temperature Range: -60°C to +80°C.
- Assembly Instruction Sheet: AI 300 (Sizes Os to F) and AI 303 (Sizes G to J).
- Alternative certifi cation options available:
Features
- Provides armour clamping using one clamping arrangement for all armour / braid types.
- Provides a diaphragm seal on inner sheath of cable which will not damage cables that exhibit ‘Cold Flow’ characteristics.
- Provides an outer deluge seal to prevent moisture ingress to the cable armour / braid.
- Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.
- Manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium.
- Brass NPT entries are nickel plated as standard.
Alternative certification options available
Attention: The internal data of table “75” is corrupted!
Steel Wire Armour / Braid / Tape
Size Ref. | Steel Wire Armour / Braid / Tape | |
---|---|---|
Orientation 1 | Orientation 2 | |
B | 0.9 - 1.25 | 0.5 - 0.9 |
C | 1.2 - 1.6 | 0.6 - 1.2 |
C2 | 1.2 - 1.6 | 0.6 - 1.2 |
D | 1.45 - 1.8 | 1.0 - 1.45 |
E | 1.45 - 1.8 | 1.0 - 1.45 |
F | 1.45 - 1.8 | 1.0 - 1.45 |
Ordering Information
Format for ordering is as follows: Alternate Clamping Ring (S), add suffi x S to ordering information.
Cable Gland Type | Size | Thread | (OPTIONAL) | Cable Gland Type | Size | Thread | (OPTIONAL) |
---|---|---|---|---|---|---|---|
501/453/UNI | C | M32 | AR | 501/453/UNI | C | 1¼" NPT | AR |
Download as PDF