Technical Resources
We have gathered together a number of technical resources for use as reference on electrical projects.
DISCLAIMER: The information on this page and the PDF is for information only and R&M Electrical Group Ltd can not be held liable for any information therein.
501/421 Hazardous Area Cable Gland
Flameproof Exd & Increased Safety Exe Dual Certified ATEX / IECEx
Download as PDF
Application
The 501/421 cable gland provides a seal on the outer cable sheath and is intended for use on non-armoured elastomer and plastic insulated cables. The cable gland is dual certified Exd and Exe and is suitable for installation in Zone 1 (21) and Zone 2 (22) hazardous areas.

Cable Gland Selection Table
Size Ref. | Entry Thread Size C | Cable Acceptance Details | 'G' | Hexagon Dimensions | |||||
---|---|---|---|---|---|---|---|---|---|
Metric | NPT * Standard or Option | Outer Sheath 'B' | Across Flats | Across Corners |
|||||
Standard Seal | Alternative Seal (S) |
||||||||
Min. | Max. | Min. | Max. | ||||||
2K | M16 | 3.0 | 8.0 | 23.5 | 19.0 | 21.2 | |||
Os | M20² | ½" | 3.0 | 8.0 | 23.8 | 24.0 | 26.5 | ||
O | M20² | ½" | 7.5 | 11.9 | 23.8 | 24.0 | 26.5 | ||
A | M20 | ¾" or ½" | 11.0 | 14.3 | 8.5 | 13.5 | 24.8 | 30.0 | 32.5 |
B | M25 | 1" or ¾" | 13.0 | 20.2 | 9.5 | 15.4 | 25.8 | 36.0 | 39.5 |
C | M32 | 1¼" or 1" | 19.0 | 26.5 | 15.5 | 21.2 | 28.2 | 46.0 | 50.5 |
C2 | M40 | 1½" or 1¼" | 25.0 | 32.5 | 22.0 | 28.0 | 29.5 | 55.0 | 60.6 |
D | M50 | 2" or 1½" | 31.5 | 44.4 / 42.3² | 27.5 | 34.8 | 0.4 | 65.0 | 70.8 |
E | M63 | 2½" or 2" | 42.5 | 56.3 / 54.3² | 39.0 | 46.5 | 38.2 | 80.0 | 88.0 |
F | M75 | 3" or 2½" | 54.5 | 68.2 / 65.3² | 48.5 | 58.3 | 40.5 | 95.0 | 104.0 |
G | M80 | 3½" | 67.0 | 73.0 | 41.0 | 106.4 | 115.0 | ||
H | M90 | 3½" | 67.0 | 77.6 | 41.0 | 115.0 | 130.0 | ||
J | M100 | 4" | 75.0 | 91.6 | 41.0 | 127.0 | 142.0 |
All dimensions in millimeters (except * where dimensions are in inches). 2K – F size metric entry threads are 1.5mm pitch as standard, 15mm length of thread. For G size glands and above, a 2mm pitch is supplied as standard, 20mm length of thread (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering.
Smaller value is applicable when selecting reduced NPT entry option.
² Sizes Os and O are available with an M16 thread size. For O size with M16 thread, the maximum cable outer sheath diameter is 10.9mm
Technical Data
- Flameproof Exd and Increased Safety Exe II 2 GD ExtD A21.
- Certificate No’s: Baseefa06ATEX0056X and IECEx BAS 06.0013X.
- Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC.
- Construction and Test Standards: IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 61241-0 and IEC/EN 61241-1.
- Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X.
- Deluge Protection to DTS01.
- Operating Temperature Range: -60°C to +100°C.
- Assembly Instruction Sheet: AI 307.
Alternative certification options available
Features
- When used in Increased Safety applications, this cable gland may be used with braided cable where the braid and the outer sheath pass into the enclosure. The braid must then be suitably terminated inside the enclosure.
- Manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminium.
- Brass NPT entries are nickel plated as standard.
Ordering Information
Format for ordering is as follows: Alternate Clamping Ring (S), add suffi x S to ordering information.
Cable Gland Type | Size | Thread | (OPTIONAL) | Cable Gland Type | Size | Thread | (OPTIONAL) |
---|---|---|---|---|---|---|---|
501/421 | C | M32 | S | 501/421 | C | 1¼" NPT | S |
Download as PDF